Exam: 006830rr – transformers and special locations

Exam: 006830RR – Transformers and Special Locations

 

1. With the exception of class 2 or class 3 transformers, if the disconnecting means for a transformer is not in sight of the transformer, the disconnecting means is required to be

A. lockable.

B. weatherproof.

C. moisture resistant.

D. bonded.

 

2. Two electricians are discussing guarding requirements for transformers. Electrician A says that a warning sign indicating the operating voltage of live parts on a transformer is required if the live parts are exposed. Electrician B says that dry-type transformers can be installed without an enclosure. Which of the following statements is correct?

A. Neither electrician is correct.

B. Both electricians are correct.

C. Only Electrician A is correct.

D. Only Electrician B is correct.

 

3. Which of the following is a NEC violation for wiring installed in a place of assembly?

A. Permanent wiring using AC cable containing an insulated EGC

B. Permanent wiring in nonmetallic raceway encased by one inch of concrete

C. Temporary wiring laid directly on the floor

D. Temporary wiring not protected by GFCIs

 

4. In Class II, Division 2, conditions fuses, switches, circuit breakers, and similar devices must be installed in enclosures that are

A. vapor proof.

B. airtight.

C. dust tight.

D. watertight.

 

5. A hazardous location in which flammable gases or vapors exist in sufficient quantities to cause an explosion, as defined by the NEC?

A. Class I

B. Unclassified

C. Class III

D. Class II

 

6. Two electricians are discussing hazardous locations. Electrician A says that hazardous location classifications are determined by the presence of gases, dust, or ignitable fibers. Electrician B says that division 2 conditions would not create a fire or explosion under normal circumstances. Which of the following statements is correct?

A. Both electricians are correct.

B. Neither electrician is correct.

C. Only Electrician A is correct.

D. Only Electrician B is correct.

 

 

 

 

 

7. Two electricians are discussing special requirements for health care facilities. Electrician A says that a nursing home is required to include an emergency system circuit. Electrician B says that GFCI outlets are not required in the bathroom area of some critical-care patient rooms. Which of the following statements is correct?

A. Both electricians are correct.

B. Neither electrician is correct.

C. Only Electrician B is correct.

D. Only Electrician A is correct.

 

8. Ignoring any exceptions, which of the following transformer types is not required to be installed in a vault?

A. Dry-type, indoor, rated over 35 kV

B. Dry-type, indoor, rated 1121/2 kVA or less

C. Oil-insulated, installed indoors

D. Nonflammable fluid-insulated, insulated rated over 35 kV

 

9. According to the NEC, conduit seals are required within _______ inches from a pressurized enclosure when the conduit is not pressurized in Class I, Division 1 protection systems.

A. 24

B. 30

C. 12

D. 18

 

10. To be in compliance with the NEC, transformer vaults must have a fire-resistance rating of _______hours and concrete floors that are at least _______ inches thick, unless protected by automatic sprinkler systems.

A. 2, 3

B. 1, 3

C. 3, 4

D. 4, 4

 

11. What hazardous location designation applies to facilities where flammable gases are handled, processed or used, but under normal circumstances there is not a threat of explosion?

A. Class II, Division 2

B. Class I, Division 1

C. Class I, Division 2

D. Class II, Division 1

 

12. What size primary fuse is required to protect a 5 kVA, 208 V, 3Φ transformer?

A. 17.5 A

B. 13.5 A

C. 15 A

D. 20 A

 

13. Two electricians are discussing transformers. Electrician A says that to insure proper ventilation, the required clearances can be found on the transformer nameplate markings. Electrician B says that exposed live parts on a transformer require the installation of a sign that indicates the operating voltage. Which of the following statements is correct?

A. Only Electrician A is correct.

B. Only Electrician B is correct.

C. Both electricians are correct.

D. Neither electrician is correct.

 

14. What article in the NEC would you reference to determine the wiring requirements for a local dinner theater?

A. Article 520

B. Article 525

C. Article 522

D. Article 530

 

15. Lighting fixtures used in Class III, Division 1 and Division 2 locations are required to be marked with the maximum lamp wattage that can be used without exceeding a fixture surface temperature of _______° F.

A. 165

B. 329

C. 453

D. 250

 

16. What is the T Code for equipment having a maximum surface temperature of 392°F?

A. T4

B. T3A

C. T3

D. T4A

 

17. What size maximum level of primary-only overcurrent protection is required for a 600-volt transformer with a primary current rating of 54 amperes?

A. 70

B. 60

C. 100

D. 50

 

18. All 15 A and 20 A, 125 V receptacles installed in a pediatric playroom in a health care facility must be _______ receptacles.

A. GFCI

B. tamper-resistant

C. nongrounding

D. standard

 

19. What is the maximum size fuse that may be used to protect a 60 kVA, nonsupervised transformer

having a 4,160 V primary and 5% impedance?

A. 35 A

B. 20 A

C. 30 A

D. 25 A

 

20. Which of the following is not a consideration when installing a LFLI transformer indoors?

A. Pressure relief vent

B. Automatic fire extinguishing system

C. Voltage rating

D. Building type

 

 

Calculate the price of your order

Select your paper details and see how much our professional writing services will cost.

We`ll send you the first draft for approval by at
Price: $36
  • Freebies
  • Format
  • Formatting (MLA, APA, Chicago, custom, etc.)
  • Title page & bibliography
  • 24/7 customer support
  • Amendments to your paper when they are needed
  • Chat with your writer
  • 275 word/double-spaced page
  • 12 point Arial/Times New Roman
  • Double, single, and custom spacing
  • We care about originality

    Our custom human-written papers from top essay writers are always free from plagiarism.

  • We protect your privacy

    Your data and payment info stay secured every time you get our help from an essay writer.

  • You control your money

    Your money is safe with us. If your plans change, you can get it sent back to your card.

How it works

  1. 1
    You give us the details
    Complete a brief order form to tell us what kind of paper you need.
  2. 2
    We find you a top writer
    One of the best experts in your discipline starts working on your essay.
  3. 3
    You get the paper done
    Enjoy writing that meets your demands and high academic standards!

Samples from our advanced writers

Check out some essay pieces from our best essay writers before your place an order. They will help you better understand what our service can do for you.

Perks of our essay writing service

We offer more than just hand-crafted papers customized for you. Here are more of our greatest perks.

  • Swift delivery
    Our writing service can deliver your short and urgent papers in just 4 hours!
  • Professional touch
    We find you a pro writer who knows all the ins and outs of your subject.
  • Easy order placing/tracking
    Create a new order and check on its progress at any time in your dashboard.
  • Help with any kind of paper
    Need a PhD thesis, research project, or a two-page essay? For you, we can do it all.
  • Experts in 80+ subjects
    Our pro writers can help you with anything, from nursing to business studies.
  • Calculations and code
    We also do math, write code, and solve problems in 30+ STEM disciplines.

Frequently asked questions

Get instant answers to the questions that students ask most often.

See full FAQ
    See full FAQ

    Take your studies to the next level with our experienced specialists

    WhatsApp
    Hello, Send us a message or inquiry, and we will respond right away